Good lighting is essential in all building interiors β it helps work to be done efficiently and safely and plays an important part in creating pleasant, comfortable surroundings. Before studying lighting technology, we must define the fundamental quantities.
Definition
Luminous Intensity (I) β The illuminating power of a light source to radiate luminous flux in a particular direction. The earliest unit was candle power (based on a wax candle). The SI unit is the candela (cd).
Definition
Luminous Flux (F) β The total flow of light radiated from a source in all directions. The SI unit is the lumen (lm). One lumen is the light flux emitted within a unit solid angle (cone) from a point source of 1 candela.
Definition
Illuminance (E) β A measure of the light falling on (incident upon) a surface. The SI unit is the lux (lx). 1 lux = 1 lumen falling on an area of 1 mΒ².
Definition
Luminance (L) β A measure of the brightness of a surface β the light reflected from or emitted by a surface towards the eye. Units vary: for diffusing surfaces (e.g. matt white paint) the unit is lumen per mΒ²; for polished surfaces (e.g. reflectors) it is candela per mΒ².
Definition
Lamp Efficacy β The ratio of luminous flux output (lumens) to electrical power consumed (watts). Measured in lumens per watt (lm/W). The higher the efficacy, the more efficiently the lamp converts electricity into light.
Definition
Colour Rendering β The ability of a light source to reproduce the natural colours of objects as they would appear in daylight. A lamp can only show a colour if it emits light at that colour's frequency.
Definition
Luminaire β The modern term for the complete light fitting β the equipment that supports and surrounds the lamp and may control the distribution of light. The 18th Edition IET Regulations (411.3.4) require all luminaire circuits in domestic premises to be protected by a 30 mA RCD.
Figure 1 β How the key lighting quantities relate to the lamp, the surface and the observer's eye.
2. Illumination Laws
The Inverse Square Law
Rays of light falling upon a surface from a distance d will illuminate that surface with a certain illuminance. If the distance is doubled, the same luminous flux spreads over four times the area β so the illuminance falls to one quarter. This relationship is the Inverse Square Law.
INVERSE SQUARE LAW
E = I / dΒ² (lux)
Where: E = illuminance (lx), I = luminous intensity (cd), d = distance from source to surface (m).
Figure 2 β The inverse square law: double the distance = ΒΌ the illuminance.
If a lamp's distance to a surface is doubled, its illuminance is reduced by a factor of 4 (not 2). If trebled, the illuminance falls to 1/9.
The Cosine Law
When a surface is tilted at an angle ΞΈ to the perpendicular rays of light, the same flux is spread over a larger area. The illuminance is reduced by the factor cos ΞΈ.
COSINE LAW
E = (I Γ cos ΞΈ) / dΒ² (lux)
Figure 3 β The cosine law: light at an angle ΞΈ produces less illuminance than light directly below.
Use the inverse square law (E = I/dΒ²) for the point directly below the lamp. Use the cosine law (E = I cos ΞΈ / dΒ²) for any point offset at an angle.
3. Worked Examples β Illumination Calculations
Example 1 β Inverse Square Law (Direct)
A lamp of luminous intensity 1000 cd is suspended 2 m above a laboratory bench. Calculate the illuminance directly below the lamp.
Formula: E = I / dΒ²
Substitute: E = 1000 / (2)Β² = 1000 / 4
E = 250 lux
Example 2 β Cosine Law (Offset Point)
A street lantern has a 2000 cd light source suspended 4 m above the ground. Determine the illuminance (a) directly below the lamp and (b) at a point 3 m to one side.
(a) Directly below β Point A:
Formula: E = I / dΒ²
Substitute: E = 2000 / (4)Β² = 2000 / 16
EA = 125 lux
(b) At point B, 3 m to one side:
Step 1 β Find distance d (Pythagoras): d = β(4Β² + 3Β²) = β(16 + 9) = β25 = 5 m
Step 2 β Find cos ΞΈ: cos ΞΈ = adjacent / hypotenuse = 4 / 5 = 0.8
Step 3 β Apply cosine law: E = (I Γ cos ΞΈ) / dΒ² = (2000 Γ 0.8) / 5Β² = 1600 / 25
EB = 64 lux
Example 3 β Finding Intensity and Distance
A discharge lamp is suspended 4 m above a bench. The illuminance directly below is 300 lx. Find (a) the luminous intensity and (b) the distance along the bench where the illuminance falls to 153.6 lx.
(a) Find I:
Rearrange: I = E Γ dΒ²
Substitute: I = 300 Γ 4Β² = 300 Γ 16
I = 4800 cd
(b) Find horizontal distance x where E = 153.6 lx:
Use cosine law rearranged: E = (I Γ cos ΞΈ) / dΒ² where cos ΞΈ = h/d = 4/d
Rearrange: dΒ³ = 19200 / 153.6 = 125, so d = β125 = 5 m
Find x (Pythagoras): x = β(5Β² β 4Β²) = β(25 β 16) = β9
x = 3 m along the bench
Example 4 β Quick Practice
A lamp of 800 cd is mounted 5 m above a factory floor. What is the illuminance directly below?
E = 800 / 5Β² = 800 / 25
E = 32 lux
Example 5 β Cosine Law Practice
Using the lamp from Example 4 (800 cd, 5 m height), find the illuminance at a point 4 m horizontally from the base.
Find d: d = β(5Β² + 4Β²) = β(25 + 16) = β41 β 6.40 m
Find cos ΞΈ: cos ΞΈ = 5 / 6.40 β 0.781
Apply: E = (800 Γ 0.781) / 6.40Β² = 624.8 / 41
E β 15.24 lux
Recommended Illuminance Levels (IES)
Task
Working Situation
Illuminance (lx)
Casual vision
Storage rooms, stairs, washrooms
100
Rough assembly
Workshops, garages
300
Reading / writing / drawing
Classrooms, offices
500
Fine assembly
Electronic component assembly
1000
Minute assembly
Watch making
3000
4. The Lumen Method
The inverse square law is suitable for outdoor schemes with no reflecting surfaces. For interior lighting, light reflected from walls and ceilings adds secondary illumination. The most widely used method for interior design is the Lumen Method.
LUMEN METHOD
Number of luminaires = (E Γ A) / (F Γ UF Γ LLF)
Where:
E = required illuminance (lx) β from IES code or architect's specification
A = total working area (mΒ²)
F = lumen output of each luminaire (lm) β from manufacturer's data
UF = Utilisation Factor (always < 1, typically 0.9) β accounts for light absorbed by surfaces
LLF = Light Loss Factor (typically 0.8β0.9) β accounts for dirt, ageing and lamp depreciation
The LLF combines four separate losses: Luminaire Dirt Depreciation (LDD), Room Dirt Depreciation (RDD), Lamp Failure Factor (LFF), and Lamp Lumen Depreciation (LLD). Always use the manufacturer's initial lamp lumens because the LLF already accounts for depreciation over time.
Example 6 β Lumen Method Calculation
An electronic workshop measuring 9 m Γ 8 m Γ 3 m requires illumination of 550 lx at bench level. Each luminaire uses one 1500 mm 65 W natural tube with an initial output of 3700 lumens. UF = 0.9, LLF = 0.8. How many luminaires are needed?
A classroom measures 12 m Γ 8 m and requires 500 lx. Each luminaire provides 5100 lumens (white tube). UF = 0.85, LLF = 0.8. How many luminaires?
N = (500 Γ 12 Γ 8) / (5100 Γ 0.85 Γ 0.8)
N = 48,000 / 3,468 = 13.84
14 luminaires required
Characteristics of a 1500 mm 65 W Bi-Pin Fluorescent Tube
Tube Colour
Initial Lumens
Design Lumens
Colour Rendering
Appearance
Artificial daylight
2600
2100
Excellent
Cool
De luxe natural
2900
2500
Very good
Intermediate
De luxe warm white
3500
3200
Good
Warm
Natural
3700
3400
Good
Intermediate
Daylight
4800
4450
Fair
Cool
Warm white
4950
4600
Fair
Warm
White
5100
4750
Fair
Warm
Initial lumens measured after 100 hours. Design lumens measured after 2000 hours. Rated life: 7500 hours. Efficacy: 30β70 lm/W.
5. Classification of Lamps
Lamps are broadly classified into two families based on how they create light:
Figure 4 β Family tree of electric lamp types.
GLS (General Lighting Service) Lamps
GLS lamps produce light by the heating effect of an electric current. A fine tungsten wire is coiled and coiled again (coiled-coil) to form the incandescent filament. This arrangement reduces filament cooling and increases light output by allowing a higher operating temperature. Most electricity is converted to heat, with only a small proportion producing light.
GLS Filament Lamp
Efficacy: 14 lm/WLife: 1000 hoursColour rendering: Fairly goodLight colour: Warm white to yellowHow it works: Heating a tungsten filament until white-hot (incandescence)
Incandescent
Tungsten Halogen Lamps & the Halogen Cycle
Standard GLS lamps suffer from tungsten evaporation β the filament gets thinner, the bulb wall darkens, and eventually the filament fails. The tungsten halogen lamp overcomes this with a clever regeneration cycle.
The glass envelope contains a trace of halogen gas (iodine, chlorine, bromine or fluorine). Evaporated tungsten combines with the halogen near the cooler bulb wall, forming a tungsten halide compound. This drifts back towards the hot filament where it breaks apart, redepositing the tungsten onto the filament and releasing the halogen for another cycle.
Figure 5 β The halogen regeneration cycle prevents bulb blackening and extends lamp life.
Tungsten Halogen Lamp
Efficacy: 20 lm/WLife: 2000 hoursColour rendering: GoodLight colour: Very white, intenseCaution: Never touch with bare hands β grease causes cracking
Incandescent β Halogen Cycle
Tungsten Halogen Dichroic Spot
Efficacy: 20 lm/WLife: 2000 hoursAvailable as: 12 V bi-pin (20/35/50 W), 230 V GU10/GZ10 (20/35/50 W)Application: Commercial & domestic spotlighting
Incandescent β Dichroic
6. Discharge Lamps
Discharge lamps do not use an incandescent filament. Instead, light is produced by the excitation of a gas or metallic vapour contained within a glass envelope. A voltage applied to two electrodes sealed into the tube excites the gas and produces light directly. The colour depends on the gas or vapour used:
Mercury β BlueSodium β YellowMagnesium β Grass Green
Fluorescent Lamps
Fluorescent lamps are linear arc tubes, internally coated with fluorescent phosphor powder, containing low-pressure mercury vapour and argon gas.
Figure 6 β How a fluorescent lamp creates visible light through UV conversion.
Compact Fluorescent Lamps (CFLs)
CFLs are miniature fluorescent lamps designed to replace ordinary GLS lamps. Available in stick, spiral and double-D shapes to fit existing fittings. They use the same discharge principle but are much more compact and energy-efficient.
High-Pressure Mercury Vapour Lamp (MBF)
The discharge takes place in a quartz glass arc tube inside an outer bulb coated with fluorescent powder. Contains mercury vapour and argon gas. Takes 5β7 minutes to reach full brightness. If switched off, it cannot restrike until the pressure drops (another ~5 minutes).
Mercury Vapour (MBF)
Efficacy: 38β56 lm/WLife: 7500 hoursColour rendering: Fairly good (cold appearance)Applications: Street lighting, shopping centres, area floodlightingWarm-up: 5β7 minutes to full brightness
Discharge β Mercury
Low-Pressure Sodium Lamp (SOX)
The discharge takes place in a U-shaped arc tube of special sodium-resistant glass, encased in a clear glass outer bulb. Cannot start in sodium alone β neon gas starts the initial red discharge which heats the sodium over 6β11 minutes until the lamp turns bright yellow. Must be operated horizontally.
Low-Pressure Sodium (SOX)
Efficacy: 61β160 lm/W (very high)Life: 6000 hoursColour rendering: Very poor (yellow only)Position: Horizontal or within 20Β° of horizontalApplications: Street and motorway lighting
Discharge β Sodium LP
The SOX lamp has the highest efficacy of all discharge lamps because sodium light's wavelength is close to the peak sensitivity of the human eye. However, its colour rendering is very poor β everything looks yellow.
High-Pressure Sodium Lamp (SON)
The discharge occurs in a sintered aluminium oxide arc tube (the only material that can withstand sodium at high pressure). An electronic pulse igniter (2 kV+) starts the lamp. Takes ~5β7 minutes to reach full brightness. Produces a pleasant golden-white light.
High-Pressure Sodium (SON)
Efficacy: 100β120 lm/WLife: 6000 hoursColour rendering: Fair (warm, golden)Position: UniversalApplications: Food halls, hotel receptions, factories, airports, car parks
Discharge β Sodium HP
Lamp Comparison Summary
Lamp Type
Efficacy (lm/W)
Rated Life (h)
Colour Rendering
Warm-up
GLS Filament
14
1000
Fairly good
Instant
Tungsten Halogen
20
2000
Good
Instant
Fluorescent Tube
30β70
7500
Fair to Excellent
Seconds
Mercury Vapour (MBF)
38β56
7500
Fairly good
5β7 min
LP Sodium (SOX)
61β160
6000
Very poor
6β11 min
HP Sodium (SON)
100β120
6000
Fair
5β7 min
LED
80β150+
25,000β50,000+
Good
Instant
7. LED Lamps
A light emitting diode (LED) is a very small semiconductor source of illumination. It is a P-N junction diode that emits photons of light when activated β a process called electroluminescence.
Figure 7 β LED principle: electrons crossing the P-N junction release photons of light. Colour temperature measured in Kelvin.
Advantages of LED lamps: Very low energy consumption, very long life (25,000β50,000+ hours), small size, greater robustness, instant start, available in Edison Screw, Bayonet Cap, Bi-Pin, GU10 and GX53 fittings.
Colour temperature: Measured in Kelvin (K). A 2,700K lamp gives a warm yellow/white light (similar to GLS). A 3,000K+ lamp gives a bright white light suitable for kitchens and clinical environments.
LED lamps and strips can exhibit flickering and stroboscopic effects similar to discharge lamps. Electrical designers must be aware of this.
8. Control Gear & Starting Circuits
Discharge lamps require additional control gear for safe and efficient operation. All discharge circuits are inductive and require power factor correction (usually a capacitor across the supply).
Switch-Start Fluorescent Lamp Circuit
The most common circuit, using a glow-type starter switch:
Quick-Start Fluorescent Lamp Circuit
Uses a small auto-transformer to heat the cathodes continuously. After a short pre-heating period, the mercury vapour ionises and the arc strikes. An earthed metal strip near the tube assists starting. No starter switch is needed. The choke limits current; a capacitor provides PF correction.
Advantage: Faster, more reliable starting than switch-start.
Semi-Resonant Start Circuit
A specially wound transformer replaces the choke. Primary and secondary windings are wound in opposition (180Β° out of phase), boosting the voltage across the tube. The electron cloud forms quickly and the arc strikes very easily β even at temperatures as low as β5Β°C.
Key advantage: No PF correction capacitor needed β the circuit is predominantly capacitive with a naturally high power factor.
Control Gear for Discharge Lamps
Each discharge lamp type requires specific control gear:
Lamp
Control Gear
Starting Method
Mercury Vapour (MBF)
Choke ballast + PF capacitor
Starting electrode near main electrode
LP Sodium (SOX)
Transformer ballast + PF capacitor
Leakage transformer applies ~2Γ mains voltage
HP Sodium (SON)
Choke ballast + ignitor + PF capacitor
Electronic pulse igniter (2 kV+)
Loading of Discharge Circuits
Discharge circuits must carry the total steady current (lamp + control gear). Where exact data is unavailable, the On-Site Guide states that the rating of final circuits for discharge lamps may be taken as:
An 80 W fluorescent lamp luminaire: Assumed demand = 80 Γ 1.8 = 144 W
The functional switch rating should be twice the total steady current of the inductive circuit to withstand the excessive contact wear caused by the inductive load.
9. Stroboscopic Effect
All discharge lamps on a.c. circuits flicker because the arc is extinguished every half-cycle as the current passes through zero. This can cause rotating or reciprocating machinery to appear stationary or running at the wrong speed β an extremely dangerous effect called the stroboscopic effect (IET Regulation 559.9).
Figure 8 β The stroboscopic effect: discharge lamps flicker 100 times per second on a 50 Hz supply. The lead-lag circuit eliminates this.
10. Installation & Maintenance
Installation Considerations
Discharge lamps may have restrictions on their operating position. The luminaire must suit the environment β corrosive, outdoor, low-temperature or decorative. Vibration causes premature lamp failure. Control gear must be rigidly fixed; plasterboard or wooden panels can amplify choke noise. Self-contained luminaires must have an adjacent means of isolation in addition to the functional switch (Reg. 537.2). Control gear must be in non-combustible enclosures or positioned to allow heat dissipation (Reg. 559.4.1).
Maintenance β Spot vs Group Replacement
Spot Replacement
Replace individual lamps as they failBest for: small installations (shops, offices, domestic)Disadvantage: repeated small disturbances
Group Replacement
Replace all lamps at the same scheduled timeBased on manufacturer's rated life + operating hoursBest for: big stores, major retail (done at night/weekends)Advantage: reduced labour costs and disruption
11. Power Consumption, kWh & Design Rating
What is a Kilowatt-Hour (kWh)?
Electricity is sold in units of energy, not power. The unit of electrical energy used for billing is the kilowatt-hour (kWh), often simply called a "unit" of electricity. One kWh is the energy consumed when a load of 1 kW operates for 1 hour.
ENERGY CONSUMED
Energy (kWh) = Power (kW) Γ Time (hours)
Definition
Power (P) β The rate at which electrical energy is consumed or converted. Measured in watts (W) or kilowatts (kW). 1 kW = 1000 W.
Definition
Kilowatt-Hour (kWh) β A unit of energy equal to 1000 watts used for 1 hour. This is the "unit" shown on electricity bills. Cost = kWh Γ price per unit.
To convert watts to kilowatts, divide by 1000. Always convert to kW before calculating kWh.
Figure 9 β The relationship between power, time and energy (kWh).
Basic Power Consumption Calculations
Example 9 β Simple kWh Calculation
A 100 W GLS lamp is left on for 8 hours. How much energy does it consume?
Convert to kW: 100 W Γ· 1000 = 0.1 kW
Apply formula: Energy = 0.1 kW Γ 8 h
Energy = 0.8 kWh
Example 10 β Comparing GLS vs LED
A householder replaces a 60 W GLS lamp with a 7 W LED lamp that gives the same light output. Both are used for 5 hours per day for 365 days. Electricity costs 34p per kWh. What is the annual saving?
Annual saving = Β£37.23 β Β£4.34 = Β£32.89 per lamp
Design Rating of Discharge Lamps β The 1.8 Multiplier
When calculating the electrical loading of discharge lamp circuits, the power consumed is not just the lamp wattage. The control gear (chokes, ballasts, transformers, ignitors) also consumes power. The On-Site Guide (Appendix 1) states:
The Γ1.8 multiplier accounts for the additional current drawn by the control gear (choke/ballast) and the low power factor of the inductive circuit. This must be used when sizing cables, protective devices and switches for discharge lighting circuits, unless more accurate manufacturer's data is available.
Figure 10 β The Γ1.8 multiplier accounts for control gear losses and poor power factor.
Example 11 β Design Rating of a Single Discharge Lamp
A luminaire contains a 65 W fluorescent tube. What is its assumed demand for circuit design purposes?
Apply Γ1.8: 65 W Γ 1.8
Assumed demand = 117 W
Example 12 β Design Current for a Discharge Lighting Circuit
A single-phase 230 V circuit supplies 12 fluorescent luminaires, each with a 58 W tube. Calculate the design current (Ib) of the circuit.
Step 1 β Total rated wattage: 12 Γ 58 = 696 W
Step 2 β Apply Γ1.8 for discharge lamps: 696 Γ 1.8 = 1252.8 W
Step 3 β Design current: Ib = P / V = 1252.8 / 230
Ib = 5.45 A
Example 13 β Energy Cost with Γ1.8 Multiplier
A workshop has 15 luminaires each containing an 80 W fluorescent tube. The workshop operates 8 hours/day, 5 days/week, 50 weeks/year. Electricity costs 34p per kWh. Calculate the annual energy cost using the Γ1.8 multiplier.
Difference = Β£652.80/year β ignoring the Γ1.8 significantly underestimates the true energy cost
Example 15 β Mixed Lamp Types on a Circuit
A retail unit has 8 Γ 100 W GLS lamps and 6 Γ 70 W SON discharge lamps, all on a single-phase 230 V supply. Calculate the total design current.
GLS (no multiplier): 8 Γ 100 = 800 W
SON (Γ1.8): 6 Γ 70 Γ 1.8 = 756 W
Total assumed demand: 800 + 756 = 1556 W
Design current: Ib = 1556 / 230
Ib = 6.77 A
Note: The Γ1.8 only applies to discharge lamps (fluorescent, sodium, mercury). GLS and LED lamps use their rated wattage directly.
Summary β When to Apply Γ1.8
Lamp Type
Apply Γ1.8?
Reason
GLS Filament
No
Purely resistive β no control gear
Tungsten Halogen
No
Purely resistive β no control gear
LED
No
Driver losses minimal β use rated wattage
Fluorescent Tube
Yes Γ1.8
Choke/ballast + low power factor
CFL (with external ballast)
Yes Γ1.8
Separate control gear
Mercury Vapour (MBF)
Yes Γ1.8
Choke ballast + low PF
LP Sodium (SOX)
Yes Γ1.8
Transformer ballast + low PF
HP Sodium (SON)
Yes Γ1.8
Choke + ignitor + low PF
Diversity β On-Site Guide Table 1B
When designing an individual circuit (sizing cables, selecting MCBs), you use the full design current (Ib) with no diversity β the circuit must be capable of carrying its entire connected load.
Diversity is applied at the distribution board level when calculating the maximum demand of the whole installation. It recognises that not every lamp in a building will be switched on at the same time. The On-Site Guide Table 1B gives allowances for different premises types:
Diversity reduces the maximum demand at the distribution board β it does NOT reduce the individual circuit design current (Ib). Always size each circuit's cable and protective device for the full load.
Figure 11 β Diversity applies at the distribution board level, not at individual circuit level.
On-Site Guide Table 1B β Diversity Allowances for Lighting
Type of Premises
Diversity Allowance for Lighting
Applied to
Individual domestic dwelling
66%
Total connected lighting load
Small shops, stores, offices
90%
Total connected lighting load
Hotels, boarding houses, guest houses
75%
Total connected lighting load
These percentages are applied to the total lighting current demand when calculating the maximum demand contribution of lighting at the distribution board or main switch.
Example 16 β Maximum Demand with Diversity (Retail Unit)
Using the retail unit from Example 15 β 8 Γ 100 W GLS and 6 Γ 70 W SON on a single-phase 230 V supply. Calculate: (a) the individual circuit design current, and (b) the maximum demand contribution of the lighting at the distribution board.
(a) Circuit design current (NO diversity):
GLS: 8 Γ 100 = 800 W
SON (Γ1.8): 6 Γ 70 Γ 1.8 = 756 W
Total assumed demand: 800 + 756 = 1556 W
Design current: Ib = 1556 / 230 = 6.77 A
Ib = 6.77 A β use this to size cables and MCBs
(b) Maximum demand at DB (WITH diversity):
Premises type: Small shop β Table 1B diversity = 90%
Apply diversity: 6.77 Γ 0.90 = 6.09 A
Maximum demand contribution of lighting = 6.09 A β use this when calculating the total maximum demand at the DB and sizing the main switch/cable
Example 17 β Domestic Dwelling Maximum Demand
A domestic dwelling has three lighting circuits with the following connected loads: Circuit 1 = 800 W, Circuit 2 = 600 W, Circuit 3 = 500 W (all LED/GLS β no Γ1.8 needed). Supply is single-phase 230 V. Calculate (a) each circuit's design current and (b) the total lighting maximum demand at the consumer unit.
(a) Individual circuit design currents (NO diversity):
Circuit 1: Ib = 800 / 230 = 3.48 A
Circuit 2: Ib = 600 / 230 = 2.61 A
Circuit 3: Ib = 500 / 230 = 2.17 A
Each circuit is sized individually for its full load.
(b) Maximum demand at consumer unit (WITH diversity):
Total lighting maximum demand = 5.45 A β this is the lighting contribution when calculating the overall maximum demand of the installation
Example 18 β Hotel with Discharge Lighting
A small hotel has a total connected lighting load of 40 Γ 36 W fluorescent luminaires on a single-phase 230 V supply. Calculate (a) the total connected load and (b) the lighting maximum demand at the DB.
Note the order: first apply Γ1.8 (for discharge lamps), then apply diversity (for maximum demand at the DB). These are two separate adjustments for different purposes.
π Flash Cards
Click the card to flip it. Use the buttons to navigate.
1 / 1
π Multiple Choice Questions
One question at a time. Select your answer for instant feedback and explanation.