Voltage Drop, Diversity & Cable Sizing Calculations
Voltage Drop & Cable Sizing · Diversity · Overcurrent Protection · Standard Circuits · Trunking Calculations · OSG Appendix Revision
Before you can size a cable or check voltage drop, you need to understand where these calculations sit in the overall design procedure. BS 7671, Chapter 13, Section 132 provides the framework. The designer follows these steps for every circuit:
To design a circuit safely, we follow this regulatory logic (from the 9-step checklist above):
A cable's current-carrying capacity is published for ideal conditions — a single cable at 30 °C, not touching insulation, not protected by a BS 3036 fuse. Real installations are rarely ideal, so we apply correction factors to work out how much current the cable really needs to handle. Each factor is less than 1, which increases It, meaning we may need a bigger cable.
It = the minimum tabulated cable rating you need to find in the OSG table. In = the rating of the protective device you chose in Step 2. The correction factors make It bigger than In to compensate for the real-world conditions.
| Factor | What It Represents | Where to Find It | When to Apply |
|---|---|---|---|
| Ca | Ambient temperature — a hotter environment means the cable can carry less current before its insulation overheats. | OSG Table F1 — look up the ambient temperature (left column) against the cable insulation type (top row). | Only if ambient temp > 30 °C. At 30 °C the factor is 1.0 (no correction needed). At 35 °C → 0.94. At 40 °C → 0.87. |
| Cg | Grouping — cables bunched together trap each other's heat, reducing the capacity of each one. | OSG Table F3 — look up the number of circuits grouped (left column) against the installation method. | When two or more circuits are bunched, clipped or enclosed together. A single cable run on its own needs no grouping factor. |
| Ci | Thermal insulation — insulation around the cable prevents heat from escaping, so the cable runs hotter. | OSG Table F2 — look up the length of cable surrounded by insulation. Over 0.5 m → 0.5 (the worst case — half capacity). | When the cable passes through or is surrounded by thermal insulation (e.g. loft insulation). If the cable is clear of insulation, Ci = 1. |
| Cf | Semi-enclosed fuse — a BS 3036 rewirable fuse is less accurate than a CB or cartridge fuse, so the cable needs extra headroom. | Always 0.725 (a constant from Appendix F of the OSG). | Only when the protective device is a BS 3036 semi-enclosed (rewirable) fuse. For MCBs, HBC fuses and cartridge fuses, Cf = 1. |
Once you have calculated It, you need to find a cable whose tabulated current rating is ≥ It. The table you use depends on the installation method:
Table F4 — for cables in conduit or trunking (Methods A and B), or clipped direct (Method C). This is the most commonly used table.
Table F6 — for PVC flat-profile (twin & earth) cables in insulated walls or surrounded by insulation (Method 100/101). Use this for domestic loft/wall situations.
In both tables, find the column for your installation method and read down to find the first cable size whose rating is ≥ It. That is your minimum cable size.
Selecting a cable that carries enough current is only half the job. The designer must also check that the voltage arriving at the load is close enough to 230 V. Over a long cable run, resistance causes a voltage loss — this is the voltage drop.
mV/A/m = millivolt drop per amp per metre — a physical constant of the cable size, found in the last column of OSG Table F4 or F6 (the same row as the cable you selected).
Ib = the design current (the actual load, not the device rating In).
L = the cable length in metres (the actual route, including vertical runs).
We divide by 1000 because the mV/A/m value is in millivolts, but we need the answer in Volts.
This table summarises the key data you need for cable selection and voltage drop. The current-carrying capacity columns show how the same cable has different ratings depending on how it is installed. The mV/A/m column is the value you put into the voltage drop formula.
| Cable Size (mm²) | Method C — Clipped Direct (Amps) | Method B — In Conduit/Trunking (Amps) | Method A — In Insulated Wall (Amps) | mV/A/m (Voltage Drop Factor) |
|---|---|---|---|---|
| 1.0 | 16 | 13 | 11.5 | 44 |
| 1.5 | 20 | 16.5 | 14.5 | 29 |
| 2.5 | 27 | 23 | 20 | 18 |
| 4.0 | 37 | 30 | 26 | 11 |
| 6.0 | 47 | 38 | 32 | 7.3 |
| 10.0 | 64 | 50 | 34 | 4.4 |
| 16.0 | 85 | 68 | 46 | 2.8 |
Question: A 230 V radial supplies a 16 A load (Ib) using a 20 A MCB (In). The 20 m cable is Clipped Direct (Method C) at 40 °C.
Question: A 32 A Ring (Ib = 25 A) is in Trunking (Method B) grouped with two other circuits. Length is 25 m.
Question: A 3 A lighting load (Ib) uses a 6 A MCB (In). The 30 m cable is in a loft, touching a ceiling, and is totally surrounded by 150 mm of insulation (Method 101).
Question: A 10 A heater (Ib) uses a 15 A BS 3036 fuse. The 40 m cable is Clipped Direct (Method C).
Question: A 32 A cooker (Ib = 28 A) is in Conduit in an insulated wall (Method A). Ambient temp is 35 °C and it is grouped with one other circuit for 15 m.
Shock protection ensures that if a fault occurs — for example a live conductor touches the metal casing of an appliance — the protective device disconnects the supply quickly enough to prevent a lethal electric shock. The key question the designer must answer is: is the earth fault loop impedance low enough for the device to trip within the required time?
When a fault occurs, the fault current flows in a loop — from the transformer, through the line conductor (R1), through the fault, back through the CPC (R2), through the main earthing terminal, and back to the transformer via the supply earth (Ze). The total impedance of this loop is Zs. The lower Zs is, the higher the fault current, and the faster the protective device trips.
Ze = external earth fault loop impedance (the supply side — obtained from the electricity distributor or by measurement).
R1 = resistance of the line conductor for the cable length of the circuit.
R2 = resistance of the circuit protective conductor (CPC) for the cable length of the circuit.
| Value | Source | How to Find It |
|---|---|---|
| Ze | Electricity distributor or measurement | Ask the DNO, or use the typical worst-case values: TN-S = 0.8 Ω, TN-C-S (PME) = 0.35 Ω. For TT systems the value depends on the earth electrode. |
| R1 + R2 per metre | OSG Table I1 | Look up the line conductor size (left column) against the CPC size (top row). The table gives the combined resistance in mΩ/m (milliohms per metre) at 20 °C. Multiply by the cable length to get the total. |
| Temperature correction | OSG Table I3 | Under fault conditions the cable heats up, increasing its resistance. Multiply the (R1 + R2) value by the factor from Table I3 — for 70 °C PVC cable this factor is 1.20. |
| Maximum permitted Zs | OSG Appendix B | Look up the type and rating of the protective device. For Type B MCBs use Table B6. The table gives the maximum Zs value — your calculated Zs must be equal to or less than this value. |
| Circuit Type | TN System (230 V) | TT System (230 V) |
|---|---|---|
| Final circuit ≤ 32 A | 0.4 s | 0.2 s |
| Final circuit > 32 A / Distribution | 5 s | 1 s |
| MCB Rating (A) | 6 | 10 | 16 | 20 | 25 | 32 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|---|---|---|
| Max Zs (Ω) | 7.28 | 4.37 | 2.73 | 2.19 | 1.75 | 1.37 | 1.09 | 0.88 | 0.87 |
| Line Conductor (mm²) | CPC (mm²) | R1 + R2 (mΩ/m) |
|---|---|---|
| 1.0 | 1.0 | 36.20 |
| 1.5 | 1.0 | 30.20 |
| 1.5 | 1.5 | 24.20 |
| 2.5 | 1.0 | 25.51 |
| 2.5 | 1.5 | 19.51 |
| 2.5 | 2.5 | 14.82 |
| 4.0 | 1.5 | 16.71 |
| 4.0 | 2.5 | 12.02 |
| 6.0 | 2.5 | 10.49 |
| 10.0 | 4.0 | 6.44 |
| 16.0 | 6.0 | 4.23 |
Scenario: A 20 A Type B MCB protects a radial socket circuit wired in 2.5 mm² PVC flat cable (which incorporates a 1.5 mm² CPC). The cable length is 30 m. The supply is TN-C-S (PME), so Ze = 0.35 Ω.
Scenario: A 10 kW kiln (Ib = 43.47 A) is protected by a 45 A Type B MCB. The cable is 10 mm² PVC flat cable (with a 4 mm² CPC), run for 15 m. The supply is TN-C-S and Zs has been measured on site at 0.81 Ω.
Scenario: A 6 A Type B MCB protects a lighting circuit wired in 1.5 mm² PVC flat cable (with a 1.0 mm² CPC). The cable length is 25 m. The supply is TN-S, so Ze = 0.8 Ω.
V = nominal voltage (230 V). Zs = total earth fault loop impedance.
Example: if Zs = 1.052 Ω → PFC = 230 ÷ 1.052 = 218.6 A.
The highest PFC at the origin of the installation should be recorded and compared against the breaking capacity of every protective device. For a typical 230 V single-phase domestic supply, the worst-case PFC is normally up to 16 kA.
When an earth fault occurs, a very large current flows through the CPC for a short time — until the protective device disconnects. During that time, the CPC heats up rapidly. Thermal constraint is a calculation to check whether the CPC is big enough to survive this heating without its insulation being damaged.
In PVC flat-profile (twin & earth) cable, the CPC is smaller than the line conductors. For example:
These CPC sizes are from OSG Table 7.1(i). Because the CPC is the thinnest conductor in the cable, it heats up the fastest under fault conditions — so we must check it can cope.
S = minimum cross-sectional area of the CPC (mm²) needed to survive the fault.
I = the fault current in Amperes (the prospective fault current, or the current that will flow through the CPC under fault conditions).
t = the operating time of the protective device in seconds (how long the fault current flows before the device trips).
k = a material constant for the type of conductor and insulation.
| Value | Source | How to Find It |
|---|---|---|
| I (fault current) | Calculated from Zs, or given in the question | I = V ÷ Zs (e.g. 230 ÷ 1.15 = 200 A). Or the PFC may be measured on site or stated in the question. |
| t (disconnection time) | Reg 411.3.2.2 or the device's time-current curve | For a final circuit ≤ 32 A, use 0.4 s. For circuits > 32 A on a TN system, use 5 s. For specific fault currents, the time can be read from the device's time-current characteristic curve in Appendix 3 of BS 7671 (e.g. Fig. 3A4 for MCBs, Fig. 3A2 for BS 3036 fuses). |
| k (material constant) | BS 7671 Table 54.3 | For a copper conductor with 70 °C PVC insulation (the standard domestic cable), k = 115. For 90 °C thermosetting insulation, k = 143. |
| Actual CPC size | OSG Table 7.1(i) | Look up the cable size under the "Cable size (mm²)" column to find the CPC size. For example, 2.5 mm² flat cable has a 1.5 mm² CPC. |
Calculate S using the adiabatic equation. Then compare S with the actual CPC size in the cable:
• If the actual CPC ≥ S → thermal constraint is MET ✓
• If the actual CPC < S → thermal constraint is NOT MET ✗ — a larger cable or a separate, larger CPC is needed.
Scenario: A 230 V ring main is wired in 2.5 mm² PVC cable with a separate 1.5 mm² CPC in plastic conduit. The circuit is protected by a 30 A semi-enclosed fuse (BS 3036). An earth fault loop impedance test gives Zs = 1.15 Ω.
Scenario: A TN supply feeds a domestic immersion heater wired in 2.5 mm² PVC cable incorporating a 1.5 mm² CPC. The circuit is protected by a 16 A semi-enclosed fuse (BS 3036).
Scenario: A 6 mm² PVC flat-profile cable has a 2.5 mm² CPC (from OSG Table 7.1(i)). The PFC of the circuit is 1.7 kA (1700 A) and the circuit must disconnect in 0.4 s. k = 115.
Failing any one step means the design must be revised. The most common fixes are: increasing the cable size (helps steps 5–7), shortening the cable route (helps steps 7–8), or installing an RCD (helps step 8 on TT systems).
Test your knowledge on voltage drop and cable sizing. Select an answer then check your results.
Diversity recognises that not all appliances in a building will operate at full power at the same time. For example, in a typical home, it is highly unlikely that every light, the oven, the shower, and all plug-in heaters will all be switched on simultaneously.
OSG Appendix A provides diversity factors based on years of industry experience that allow us to estimate a realistic maximum demand rather than an oversized theoretical total.
① Prevents over-engineering — avoids unnecessarily large, expensive cables and switchgear.
② Reflects realistic usage patterns — load is spread over time.
③ Balances safety and economy — the installation is safe but not wastefully oversized.
| Circuit Type | Diversity Rule |
|---|---|
| Cooking Appliance | First 10 A + 30% of remainder + 5 A if socket on cooker unit |
| Lighting | 66% of total connected load |
| Socket Outlets | 100% of largest circuit + 40% of each additional circuit |
| Space Heating | 100% of largest + 75% of remainder |
Scenario: A 32 A rated electric cooker with a socket on the control unit.
Scenario: A house has 20 LED downlights, each rated at 10 W. Total load = 200 W.
Scenario: A house with three 32 A ring final circuits (Kitchen, Downstairs, Upstairs).
Task: Using the standard cooker diversity rule, calculate the assumed demand for a 45 A rated electric range cooker. The cooker control unit does not have a socket outlet.
Task: Calculate the total assumed demand for a flat with: one 32 A Ring (sockets), one 32 A Radial (additional sockets), and one 6 A lighting circuit (actual load 4 A).
Tap / click each card to reveal the definition
Fuse: Provides local protection of the circuit from overload. Used in domestic and similar premises.
Basic Protection: A physical barrier between a person / livestock and a live part.
Fault Protection: Current flowing between exposed/extraneous conductive parts and earth — the earth path allows this current to reach the protective device.
Ib (design current) ≤ In (device rating) ≤ Iz (cable's current-carrying capacity under installed conditions).
In plain English: the device must be big enough to carry the load without nuisance tripping, but small enough to protect the cable from overheating. This is Step 2 of the 9-step design process — and the It calculation (Step 4) is how you verify that Iz is adequate.
| Device | Advantages | Disadvantages |
|---|---|---|
| Re-wireable Fuse (BS 3036) |
No moving parts · Cheap · Low replacement cost | Incorrect element size can be fitted · Slow to repair · Poor breaking capacity |
| Cartridge Fuse (BS 1361) |
No moving parts · Small physical size · Accurate current rating | Incorrect cartridge can be fitted · Not suitable for high fault current · Can be shorted out |
| MCB (BS EN 60898) |
Tamper proof · Supply quickly restored · Pre-set tripping characteristics | Expensive · Regular testing required · Has moving parts |
| Type | Trip Range | Best Suited For |
|---|---|---|
| Type B | 3–5 × In | Domestic ring mains, lighting, sockets |
| Type C | 5–10 × In | Discharge lighting in large premises (e.g. supermarket) |
| Type D | 10–20 × In | Welding and X-ray machines (large in-rush currents) |
For effective discrimination, protective devices should be sized from smallest at the load to largest at the supply: e.g. 13 A at the socket → 32 A at the distribution board → 100 A at the main switch.
| Spec | A1 — Ring | A2 — Radial (20 A) | A3 — Radial (32 A) |
|---|---|---|---|
| MCB Size | 32 A | 20 A | 32 A |
| Live Cable | 2.5 mm² | 2.5 mm² | 4 mm² |
| Max Floor Area | 100 m² | 50 m² | 75 m² |
| Max Sockets | No limit | — | — |
| Rule | Detail |
|---|---|
| Non-fused spur | May only feed one single or twin socket outlet |
| Fused spurs | Unlimited number allowed from a ring |
| Fused spur fuse (BS 1362) | Must not exceed 13 A |
| Permanently connected equipment | Protected by breaker not exceeding 16 A |
| Cooker control unit distance | Within 2 m of the cooker |
| Cooker control unit position | Must not be located directly above the unit |
| Water heater (> 15 litres) | Must be on its own separate circuit |
| Socket/switch heights (new dwellings) | 450 mm to 1200 mm from floor |
| RCD protection for sockets < 20 A | 30 mA RCD required |
| Room | Small (<12 m²) | Medium (12–25 m²) | Large (>25 m²) |
|---|---|---|---|
| Living Room | 4 | 6 | 8 |
| Dining Room | 3 | 4 | 5 |
| Single Bedroom | 2 | 3 | 4 |
| Double Bedroom | 3 | 4 | 5 |
| Study | 4 | 5 | 6 |
| Kitchen | 6 | 8 | 10 |
| Bathroom | 0 | 0 | 0 |
Look up each cable's factor from the tables (e.g. Table 3.4 / OSG Table E3), multiply by the quantity, sum them, then pick a trunking size whose factor meets or exceeds that sum (Table 3.5 / OSG Table E5).
Requirement: 10 × 1.5 mm² solid PVC + 5 × 2.5 mm² solid PVC.
Requirement: 30 × 4.0 mm² stranded PVC + 20 × 6.0 mm² stranded PVC.
Requirement: 50 × 2.5 mm² stranded + 40 × 4.0 mm² stranded + 20 × 10 mm² stranded PVC.
Test yourself across all OSG Appendices (A–F). Select your answer then check your results.